Metadata-Version: 2.1
Name: thermal-mcp-server
Version: 0.2.0
Summary: MCP server for datacenter GPU liquid cooling thermal analysis
Author: Riccardo Vietri
License: MIT License
        
        Copyright (c) 2026 Riccardo Vietri
        
        Permission is hereby granted, free of charge, to any person obtaining a copy
        of this software and associated documentation files (the "Software"), to deal
        in the Software without restriction, including without limitation the rights
        to use, copy, modify, merge, publish, distribute, sublicense, and/or sell
        copies of the Software, and to permit persons to whom the Software is
        furnished to do so, subject to the following conditions:
        
        The above copyright notice and this permission notice shall be included in all
        copies or substantial portions of the Software.
        
        THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR
        IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY,
        FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE
        AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER
        LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR OTHERWISE, ARISING FROM,
        OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE
        SOFTWARE.
        
Project-URL: Homepage, https://github.com/riccardovietri/thermal-mcp-server
Project-URL: Source, https://github.com/riccardovietri/thermal-mcp-server
Project-URL: Bug Tracker, https://github.com/riccardovietri/thermal-mcp-server/issues
Keywords: mcp,thermal,cooling,gpu,datacenter,liquid-cooling,nvidia,h100,b200
Classifier: Development Status :: 4 - Beta
Classifier: Intended Audience :: Developers
Classifier: Intended Audience :: Science/Research
Classifier: License :: OSI Approved :: MIT License
Classifier: Programming Language :: Python :: 3
Classifier: Programming Language :: Python :: 3.10
Classifier: Programming Language :: Python :: 3.11
Classifier: Programming Language :: Python :: 3.12
Classifier: Topic :: Scientific/Engineering :: Physics
Classifier: Topic :: Software Development :: Libraries :: Python Modules
Requires-Python: >=3.10
Description-Content-Type: text/markdown
License-File: LICENSE
Requires-Dist: fastmcp (<3,>=2.0)
Requires-Dist: pydantic (>=2.6.0)
Provides-Extra: dev
Requires-Dist: pytest (>=8.0.0) ; extra == 'dev'
Requires-Dist: pytest-cov (>=4.1.0) ; extra == 'dev'

[![CI](https://github.com/riccardovietri/thermal-mcp-server/actions/workflows/ci.yml/badge.svg)](https://github.com/riccardovietri/thermal-mcp-server/actions/workflows/ci.yml)
[![PyPI](https://img.shields.io/pypi/v/thermal-mcp-server)](https://pypi.org/project/thermal-mcp-server/)
[![Python 3.10+](https://img.shields.io/pypi/pyversions/thermal-mcp-server)](https://pypi.org/project/thermal-mcp-server/)

# thermal-mcp-server

**An NVL72 rack dissipates 120 kW through liquid cooling. Choosing the wrong flow rate, coolant, or manifold configuration means thermal throttling (lost compute revenue) or overprovisioned cooling (wasted capex).** `thermal-mcp-server` quantifies these tradeoffs using a first-principles thermal resistance model exposed as an [MCP](https://modelcontextprotocol.io/) server.

## GPU Thermal Specs

| Chip | TDP (cold plate sizing) | Tj Design Ceiling | Source |
|------|------------------------|--------------------|--------|
| NVIDIA H100 SXM | 700 W | 83°C (throttle onset) | [NVIDIA H100 Datasheet](https://resources.nvidia.com/en-us-gpu-resources/h100-datasheet-24306) |
| NVIDIA B200 (NVL72) | 1,200 W | ~75°C (not NVIDIA-published) | [NVIDIA GB200 NVL72](https://www.nvidia.com/en-us/data-center/gb200-nvl72/), [SemiAnalysis](https://newsletter.semianalysis.com/p/gb200-hardware-architecture-and-component) |
| NVIDIA B200 (HGX standalone) | 1,000 W | Not published | [Lenovo ThinkSystem HGX B200 Product Guide](https://lenovopress.lenovo.com/lp2226-thinksystem-nvidia-b200-180gb-1000w-gpu) |
| AMD MI300X | 750 W | Not published | [AMD MI300X Data Sheet (PDF)](https://www.amd.com/content/dam/amd/en/documents/instinct-tech-docs/data-sheets/amd-instinct-mi300x-data-sheet.pdf) |
| Intel Gaudi 3 OAM | 900 W (air) / 1,200 W (liquid) | Not published | [Intel Gaudi 3 Product Brief (PDF)](https://cdrdv2-public.intel.com/817487/gaudi-3-ai-accelerator-hl-325l-oam-mezzanine-card-product-brief.pdf) |

> **Note:** TDP values are for cold plate thermal sizing, not electrical nameplate. The GB200 1,200 W figure reflects per-GPU heat dissipation in the NVL72 liquid-cooled configuration — not 120 kW / 72 amortized (which would include CPUs, NVSwitches, NICs, and VRM losses).

## Demo

Single H100 SXM cold plate analysis — 700 W, water, 10 LPM, 35°C inlet:

```python
from thermal_mcp_server.physics import analyze
from thermal_mcp_server.schemas import AnalyzeColdplateInput

result = analyze(AnalyzeColdplateInput(
    heat_load_w=700, flow_rate_lpm=10, inlet_temp_c=35.0, coolant="water"
))
```

```json
{
  "coolant": "water",
  "regime": "turbulent",
  "reynolds": 4667.6,
  "nusselt": 41.11,
  "heat_transfer_coeff_w_m2k": 24667.2,
  "pressure_drop_pa": 26503.0,
  "pump_power_w": 8.83,
  "coolant_rise_c": 1.01,
  "junction_temp_c": 80.69,
  "resistances_k_per_w": {
    "junction_to_case": 0.04,
    "tim": 0.02,
    "base_conduction": 0.00052,
    "convection": 0.00403,
    "total": 0.06455
  },
  "warnings": []
}
```

At 10 LPM water with 35°C inlet, the H100 runs at 80.7°C junction — 2.3°C of margin below the 83°C throttle point. This is a tight operating point at these inlet conditions; reducing inlet temperature to 25°C or increasing flow rate would add margin.


## How It Works

The physics engine models a single cold plate as a 1D thermal resistance network: junction-to-case (R_jc), thermal interface material (R_tim), copper base conduction, and forced convection to the coolant. Convective heat transfer uses the Dittus-Boelter correlation for turbulent flow and a constant Nu = 4.36 for laminar flow, with linear blending in the transition regime (Re 2300–4000). Pressure drop uses Darcy-Weisbach with Blasius friction factor, also blended through the transition regime. All assumptions — pump efficiency, channel geometry, property values — are documented inline in the source.

```mermaid
flowchart LR
    A["Input\nchip power, flow rate,\ncoolant, geometry"] --> B["Physics Engine\nDittus-Boelter, Darcy-Weisbach,\nR_total network"]
    B --> C["Output\nT_junction, ΔP,\nthermal margin, pump power"]
```

## Quick Start

**Install from PyPI:**

```bash
python -m venv thermal-venv
source thermal-venv/bin/activate
pip install thermal-mcp-server
```

Configure in your MCP client (e.g., Claude Desktop `claude_desktop_config.json`):

```json
{
  "mcpServers": {
    "thermal": {
      "command": "/absolute/path/to/thermal-venv/bin/python",
      "args": ["-m", "thermal_mcp_server"]
    }
  }
}
```

> **Important:** Use the absolute path to your venv's Python binary. Claude Desktop does not inherit your shell's PATH, so bare `python` will fail with "No such file or directory."

**Install from source** (for development):

```bash
git clone https://github.com/riccardovietri/thermal-mcp-server.git
cd thermal-mcp-server
python -m venv venv && source venv/bin/activate
pip install -e .
```

See the [MCP documentation](https://modelcontextprotocol.io/) for client setup details.

## Usage with Claude

Once configured, ask Claude natural-language questions about liquid cooling:

> *"I have 8 H100 SXM GPUs at 700 W each with water cooling at 8 LPM per cold plate and 25°C inlet. What's the junction temperature and am I within thermal margin?"*

Claude calls `analyze_coldplate` and interprets the result:

> *"At 8 LPM with 25°C inlet water, each H100 runs at 70.9°C junction — 12.1°C below the 83°C throttle onset. Convective resistance (0.004 K/W) is small relative to the package resistances (R_jc + R_tim = 0.06 K/W), so increasing flow rate has diminishing returns. You have room to reduce flow to ~5.5 LPM before hitting margin, which would cut pump power roughly in half."*

This works in Claude Desktop, Claude.ai with MCP, or any MCP-compatible client.

<img width="1768" height="1750" alt="image" src="https://github.com/user-attachments/assets/7e3fb436-38d2-477b-a4dd-e5a2a740d463" />

## Tools

- **`analyze_coldplate`** — Single-point thermal and hydraulic analysis. Takes heat load, flow rate, inlet temperature, coolant type, and geometry. Returns junction temperature, thermal resistances, pressure drop, and pump power.

- **`compare_coolants`** — Runs `analyze_coldplate` for water and 50/50 glycol under identical conditions. Returns side-by-side junction temperature, pressure drop, and pump power for each coolant.

- **`optimize_flow_rate`** — Binary search for the minimum flow rate that keeps junction temperature at or below a target. Returns the minimum flow rate and the full thermal analysis at that operating point.

See [docs/mcp.md](docs/mcp.md) for full input/output schemas.

## Scope

This tool models steady-state, single-cold-plate performance. Rack-level manifold modeling and transient thermal response are on the roadmap.

**Roadmap:**
- Rack-level series/parallel manifold model (NVL72 validation target: 80 LPM, 120 kW, 1.5 bar max ΔP)
- Transient thermal response (power-on ramp, workload spikes)
- Coolant cost-performance comparison (water vs. glycol vs. engineered fluids)
- Flow maldistribution sensitivity analysis